  • nik282000 2 minutes ago
    Cool, I thought grid stability attacks would rely on large numbers of IoT devices but it looks like computing infrastructure is the better target.

    Whether it's by buying and using a trillion tokens strategically or by inserting synchronized malicious jobs it should be possible to find some resonant frequencies in the line frequency control system. By loading and unloading multi-megawatts of draw you could get the local supply throttling up and down enough desynchronize from the larger grid. If you could get real time measurements of the line frequency you could use that to tune your malicious load and do the whole 'pushing a kid at the peak of their swing' thing.

    To mitigate you would have to put dummy loads or some kind of minute-scale power storage onsite or nearby to compute loads.

  • schiffern 1 hour ago
    The corresponding concept in gears is to avoid meshing two gears unless the number of teeth are co-prime, because this will cause uneven wear patterns. If the tooth counts are coprime, then each tooth will contact every tooth on the other gear the same number of times, effectively "wear leveling" the teeth.

    In this instance, one fix is to fire the timer every 59 seconds, so it will naturally drift out of phase with the minute hand of the clock. Or, if work needs to be done exactly every 60 seconds, then WAIT(RAND(60)) seconds for the timer initialization, so if 10,000 units start simultaneously they don't try all at once.

    This is why many systems will do automated updates every 17 hours: 17 is coprime with 24.

    Classic "thundering herd" mitigation tactics.

    Edit: Tempting to blame IoT, but (since this is news) I don't think anyone knew there was something to fix here. We have the tools however.

    • mkj 32 minutes ago
      59 seconds will still have second alignment. Maybe it needs to be prime milliseconds or microseconds.
    • vlovich123 37 minutes ago
      Small nit: Wait(50+rand(10)) is probably closer to what you want to get about a minute between executions. As stated your proposed execution has an average about 30s execution interval with a variance of about 17s. If you’re talking about a random sleep on a 1 minute interval, this actually results in a possibility of 120s between tasks, also not what you want.

      But yeah, as soon as you start using Rand most people make all sorts of mistakes. And if you’re using C Rand, don’t. It has other statistical problems.

      • jagged-chisel 31 minutes ago
        He’s still allowing for exactly 60s between executions. He’s saying stagger the startup by a random amount up to 60s. Then we get what we want every 60s, but they’re all just staggered a random amount.
        • vlovich123 22 minutes ago
          My bad. I misread it. Delaying the start like that does divide the thundering herd peak by 60. The point about c Rand stands.

          The other thing to watch out for is you’ve still got 1/60 of the thundering herd at the second level. If the tasks are <1s and you have enough of them (as you probably do at grid scale), then doing it finer grained is warranted like offsetting the timer by a millisecond sleep of 10 * uniform_distribution<int> between 0 and 6000. That then gives you 10ms granularity, distributing the workload by two more orders of magnitude.

          • schiffern 5 minutes ago
            I almost wrote 59.999 seconds too, but I figured someone would nitpick that the timing often won't be that accurate or will get coalesced. ;)

            Thanks, many good improvements on my very abbreviated overview! For instance you should pretty much always use randomly staggered timers on initialization, not just when the timing interval is important.

    • HPsquared 44 minutes ago
      Coprime meaning "no common factors".
  • bob1029 1 hour ago
    I'm not sure I agree with the conclusion that this is merely caused by UPS system control logic. That is an extreme amount of coordination across a lot of makes, models and configurations.

    The FFT indicates this is a periodic signal, not a once a day or week thing. It's happening continuously all day every day. I don't know of any UPS systems that perform tests with this kind of regularity.

    In any case, I refuse to believe an external sync signal is causing this. The more likely explanation is that the active elements are pulling each other to a common mode due to being physically coupled on the same grid. This is like how clocks on the same beam will synchronize.

    https://en.wikipedia.org/wiki/Injection_locking

    • the8472 1 hour ago
      The external sync here is NTP. Synchronized clocks + timer-scheduled actions → globally synchronized behavior

      From the article:

      > The origin of these current peaks was independently confirmed by the manufacturer to be periodic self-tests executed by the battery EMS, confirming our interpretation. Similar minute-scale diagnostic routines are also documented for other commercial UPS systems (cf. Supplementary Note 8).

      https://www.snaptec.com.au/akkutec-4801-din-user-manual.pdf

      > battery circuit testing 1 x per minute for 1 sec

      https://adelsystem.com/hubfs/PDF%20DC-UPS/Instruction%20Manu...

      > The battery testing is carried out automatically every 60 sec.

  • geerlingguy 1 hour ago
    I know my older APC UPSes do weekly self tests, but I guess newer equipment does more frequent self testing? And of course they're all internet-connected meaning clocks are within a few hundred ms of each other.

    It also made me think about how many GitHub Actions I have that kick off on Sunday morning at a specific time. I try to vary the time/day for those jobs but I'm guessing there are enough things that kick off at specific time intervals to make an impact at the top of an hour, or at :15, :30, :45...

    • rmunn 1 hour ago
      This is why systemd gives you the RandomizedDelaySec option. (Other cron-like facilities may have similar features, I'm not discussing them here). Set that to N and each time the timer reaches its trigger (say, once per day), its actual start will be up to N seconds after the trigger. E.g. if a once-per-day trigger is at midnight but you have RandomizedDelaySec=300 set, then it will run sometime between 0:00:00 and 0:05:00, with a different actual start time each day.

      If enough people used that, with a high enough value of N (say 1800 for jobs that really don't have to start at any particular time), it would greatly spread out the spikes in accidentally-coordinated usage.